ZMS Cable logo Get a Quote
Cable manufacturing line with coloured cable reels

Reading IEC 60227 and IEC 60228: A Buyer’s Checklist

IEC 60227 and IEC 60228 appear on many control cable datasheets. They are related, but they do not cover the same thing. Knowing which standard applies to which part of the construction makes it easier to write a purchase order that can be checked.

IEC 60228: the conductor

IEC 60228 defines the nominal cross-sectional areas and the conductor classes for cables. Class 1 is a solid conductor, Class 2 is a stranded conductor for fixed wiring, and Class 5 is a flexible stranded conductor. The class affects termination, bending and the behaviour of the cable in a moving application.

When you specify a 1.5 mm² control cable, state the conductor class. A Class 2 conductor and a Class 5 conductor are both 1.5 mm², but they are not interchangeable in every terminal or drag chain.

IEC 60227: PVC-insulated cable

IEC 60227 covers polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V. For a 300/500 V control cable, it provides the framework for insulation and sheath performance, dimensions and test requirements. The standard is not a single construction drawing; the actual core count, screen, armour and sheath are defined by the manufacturer’s datasheet and the purchase order.

What to put on the purchase order

  • Product description and application.
  • Rated voltage, core count and cross-section.
  • Conductor class and material.
  • Insulation and sheath compound.
  • Screen type, coverage and drain wire.
  • Armour type and material.
  • Applicable standard and any project specification.
  • Core identification, length, drum marking and inspection requirements.

Check the datasheet against the order

A datasheet that says “IEC 60227” is a starting point, not a complete specification. Check the conductor class, the screen coverage, the sheath thickness and the temperature rating. Ask for the order-specific datasheet before production, and confirm that the test report matches the construction that will be shipped.

Buyer’s check: the standard defines the framework; the datasheet defines the product; the purchase order defines what you will receive. Make sure all three agree.

Our team can review a specification against the proposed construction and identify the details that need to be confirmed before the order is released.

The two standards land on different products: IEC 60227 governs PVC-insulated constructions such as the general multi-core control cable, while IEC 60228 governs the conductor inside every cable we supply, including the copper braided shielded cable. Check both lines on the datasheet, not just the one named in the enquiry.