IEC 60227 and IEC 60228 appear on many control cable datasheets. They are related, but they do not cover the same thing. Knowing which standard applies to which part of the construction makes it easier to write a purchase order that can be checked.
IEC 60228: the conductor
IEC 60228 defines the nominal cross-sectional areas and the conductor classes for cables. Class 1 is a solid conductor, Class 2 is a stranded conductor for fixed wiring, and Class 5 is a flexible stranded conductor. The class affects termination, bending and the behaviour of the cable in a moving application.
When you specify a 1.5 mm² control cable, state the conductor class. A Class 2 conductor and a Class 5 conductor are both 1.5 mm², but they are not interchangeable in every terminal or drag chain.
IEC 60227: PVC-insulated cable
IEC 60227 нь 450/750 V хүртэлх үнэлгээтэй хүчдэлийн поливинил хлоридын дулаалга кабелийг багтаасан. 300/500 V хяналтын кабелийн хувьд дулаалга болон бүрхүүлтэй, бүрхэвчийн гүйцэтгэл, хэмжээс, туршилтын шаардлагыг хангадаг. Стандарт нь нэг барилгын зураг биш юм. Бодит цөм тоо, дэлгэц, хуяг дуулга, бүрээс нь үйлдвэрлэгчийн өгөгдлийн хуудас болон худалдан авалтын ордероор тодорхойлогдоно.
What to put on the purchase order
- Бүтээгдэхүүний тодорхойлолт, хэрэглээ.
- Нэрлэсэн хүчдэл, үндсэн тоо, хөндлөн огтлол.
- Conductor class and material.
- Тусгаарлалт ба бүрээсний хольц.
- Screen type, coverage and drain wire.
- Чимэглэлийн төрөл, материал.
- Applicable standard and any project specification.
- Core identification, length, drum marking and inspection requirements.
Check the datasheet against the order
A datasheet that says “IEC 60227” is a starting point, not a complete specification. Check the conductor class, the screen coverage, the sheath thickness and the temperature rating. Ask for the order-specific datasheet before production, and confirm that the test report matches the construction that will be shipped.
Our team can review a specification against the proposed construction and identify the details that need to be confirmed before the order is released.
The two standards land on different products: IEC 60227 governs PVC-insulated constructions such as the general multi-core control cable, while IEC 60228 governs the conductor inside every cable we supply, including the copper braided shielded cable. Check both lines on the datasheet, not just the one named in the enquiry.